Shop
CO2 Automatic Fire Suppression Systems
₨ 400,000 ₨ 360,000
Stabilized Over External Environment
Pipe to Run in Simple Configurations for Protection of Regular Rooms & Single Area
Safe to Use in Occupied Areas
Colorless, Odorless, Non-Contaminating Gaseous Fire Protection
Easy Installation and Maintenance
Description
CO2 Automatic Fire Suppression Systems with Solenoid Actuated Pilot Cylinder
Carbon dioxide has been used in fire fighting for over 50 years. It is generally specified in locations where people will not be working as it is hazardous to humans in the concentrations deployed by fire suppression systems.
Carbon Dioxide (CO2) smothers a fire within seconds and creates no damage to the surrounding area. Stored under pressure as liquid, 57 bars at 20°C (720 PSIG at 70°C) carbon dioxide when released through a nozzles expands to vapor then quickly and effectively permeates through the protected hazard and by reducing the oxygen in the atmosphere with its extreme density rapidly suppresses the fire.
A Carbon Dioxide Fire Suppression System consists of one or more bank of cylinder storage container. Storage containers to supply the CO2 extinguishing agent. Flexible discharge loops, or hoses, connects the cylinders to a high-pressure steel manifold. The manifold in turn distributes the agent into piping network nozzles regulate the flow of CO2 gas into the protected area.
CO2 physically extinguishes fires in two ways. Firstly, it decreases the oxygen level in the enclosure from 21% to below 15%, meaning that most fires are unable to continue combusting. Secondly the gas absorbs heat and cools the fire down.
CO2 is clean and leaves no residue, which eliminates costly after-fire clean-up and keeping expensive “downtime” to a minimum, Most materials such as steel, stainless steel, aluminum, brass and other metals as well as plastics, rubber and electronic components are unaffected by exposure to CO2.
Description:
- Container Storage Volume: 70L
- CO2 Filling: 45 Kg
- Storage Pressure: 57 Bar
- Storage Cylinders Max Working Pressure: 124 Bar
- Working Power Main Power Supply: AC 220 V / 50Hz
- Standby Power Supply: DC 24V
- NZ Power (20°C): 60 Bar
- Environment Conditions Temp: 0-50°C
- Humidity: 95%
- Activation Method: Electrical, Automatic, Manual
- Activation Delay: 0-30S adjustable
- Pilot cylinder with Solenoid valve
Masteco FM-200® (HFC-227 ea)
- Engineered automatic clean agent fire suppression Systems intended for total flooding of enclosed spaces
- UL listed & FM approved
- Made in Korea
- Fast acting suppression within 10 seconds Environmentally friendly
- Dedicated flow calculation software for Effective and reliable design by Hughes
- US DOT approved cylinders
- Proven technical service supports
- Safe for people
- Damage-free
- Designed and developed based on independently witnessed fire tests
- Agent cylinder with agent pressurized to 25 bar and a supporting nitrogen driver pressurized up to 80 bars to enhance the discharge of the agent
- Longer distances with constant pressure
- Longer pipe to run in complex configurations for protection of larger rooms & multiple areas
- Better coverage resulting in cost savings
- Easy maintenance
FM-200® (HFC-227 ea) Application
- Data & Telecommunications Centers
- Medical Facilities
- Art Galleries & Museums
- Bank Vaults
- Computer & Telephone Equipment Rooms
- Generator & Electrical Rooms
- And Many Other Applications Marine
- Oil & Gas Facilities
- Libraries & Laboratories
- Electronic Data Processing
- Robotic Systems
- Processing & Chemical Plant
Flow System Standard Solution
- Stabilized Over External Environment
- Pipe to Run in Simple Configurations for Protection of Regular Rooms & Single Area
- Safe to Use in Occupied Areas
- Colorless, Odorless, Non-Contaminating Gaseous Fire Protection
- Easy Installation and Maintenance
Agent Cylinder & Nitrogen Driver
Part No. | Nominal Capacity (L) | Agent Cylinder Valve (mm) |
Weight of Agent (kg) |
N2 Driver Pressure (bar) |
||
Agent Cylinder | N2 Driver | Agent Cylinder | N2 Driver | |||
MFC-23 | – | 27.0 | – | 40 | 13.3 – 23.6 | – |
MFC-34 | – | 40.0 | – | 40 | 19.9 – 38.4 | – |
MFC-50/P50 | N68-60 | 63.0 | 68.0 | 40 | 31.2 – 60.6 | 60 |
MFC-75/P75 | N68-70 | 89.0 | 68.0 | 40 | 44.1 – 85.6 | 70 |
MFC–100/P100 | N68-80 | 115.4 | 68.0 | 50 | 57.2 – 111.0 | 80 |
MFC-150/P150 | N68-60 | 175.0 | 68.0 | 50 | 86.7 – 168.3 | 80 |
Reviews